5.1 AUXILIARY SWITCHES
The
names of various automatic switches are:
- Level switch
- Flow switch
- Position or limit switch
- Pressure switch
- Temperature switch
- Speed switch (centrifugal switch)
IMPORTANT
LETTERS
Letters
‘a’, ‘b’, ‘aa’ and ‘bb’ are used in diagrams to represent switches or auxiliary
switches.
a-
It is closed when
main device (Circuit Breaker, Isolator or Contactor/Relay) is closed /energized
and it is opened when main device is open or de-energized. Sometimes, ‘a’ is
also called normally open contact of a device.
b-
It is closed when
main device is opened and vice versa. ‘b’ is also called normally closed
contact of a device.
aa- It is
always open. It only closes for a very short time when the driving force; (air
pressure, hydraulic pressure or spring) operating the main device is in action.
It returns to its original position when driving force ceases.
bb- It is
opposite to ‘aa’ i.e it is always closed. It opens for a very short time when
driving force operating the main device is in action. It re-closes or re-sets
when driving force is ceased
5.2 DEVICE FUNCTION NUMBERS
Function
No.
|
Type of
Relay
|
2
|
Time delay relay
|
3
|
Interlocking relay
|
21
|
Distance relay
|
25
|
Check synchronizing relay
|
27
|
Under voltage relay
|
30
|
Enunciator relay
|
32
|
Directional power
(Reverse power) relay
|
37
|
Low forward power relay
|
40
|
Field failure (loss of
excitation) relay
|
46
|
Negative phase sequence
relay
|
49
|
Machine or Transformer
Thermal relay
|
50
|
Instantaneous Over
current relay
|
51
|
A.C IDMT over current
relay
|
52
|
Circuit breaker
|
52a
|
Circuit breaker Auxiliary
switch “Normally open” (‘a’ contact)
|
52b
|
Circuit breaker Auxiliary
switch “Normally closed” (‘b’ contact)
|
55
|
Power Factor relay
|
56
|
Field Application relay
|
59
|
Overvoltage relay
|
60
|
Voltage or current
balance relay
|
64
|
Earth fault relay
|
67
|
Directional relay
|
68
|
Locking relay
|
74
|
Alarm relay
|
76
|
D.C Over current relay
|
78
|
Phase angle measuring or
out of step relay
|
79
|
AC Auto reclose relay
|
81
|
Frequency relay
|
81U
|
under frequency relay
|
81O
|
over frequency relay
|
83
|
Automatic selective
control or transfer relay
|
85
|
Carrier or pilot wire
receive relay
|
86
|
Tripping Relay
|
87
|
Differential relay
|
87G
|
Generator differential
relay
|
87GT
|
overall differential
relay
|
87U
|
UAT differential relay
|
87NT
|
Restricted earth fault
relay (provided on HV side of Generator transformer)
|
95
|
Trip circuit supervision
relay
|
99
|
Over flux relay
|
186A
|
Auto reclose lockout
relay
|
186B
|
Auto recluse lockout
relay
|
5.3 BASIC
REQUIRMENTS OF CONTROL CIRCUITS
For
circuit breakers there are a number of basic requirements which are desirable
in the control circuit. These features can be found in the motor, solenoid,
spring (stored energy) and pneumatically-operated Circuit Breakers.
A
good understanding in these control circuit features will allow an intelligent
approach to trouble-shooting. Examination of the circuit diagram of the modern
breakers will relatively complicated network of switches, contactors and coils,
the correct functioning of which is essential. Each individual component of a
circuit has a definite function to perform, thus removing any one element will
cause some type of faulty operation.
When
the maintenance electrician knows the function of each component, he also knows
what type of faulty operation to expect when that component is inoperative.
Conversely when mal-operation of a breaker is found, the likely component or
components at fault will be known.
5.3.1
CONTROL THE CLOSING
The
closing circuit must do more than merely close the breaker, it must control
this closing. To do this, the following features are necessary.
Initiate The Closing Stroke: Means must be provided in the circuit to energize the
closing device, for example, the solenoid of the solenoid-operated breaker or
the motor of a motor-operated breaker.
Cut-Off: The closing
power must be cut-off or disconnected automatically at the end of the closing
stroke. This is necessary to prevent overheating of the closing device.
Solenoid coils used on circuit breakers have only a short time rating, thus if
a closing coil is left energized for more than 15 seconds. It will overheat and
suffer damage to the insulation. For this reason it cannot be left to the
operator to decide when to cut off the closing power since it left on too long,
damage will result. The alternative where the closing power could be left on
for too short a time is covered in Seal-In.
Seal-In: It is desirable to have the
control circuit ensure that the breaker will fully close each time that closing
operation is initiated, if the breaker is closed by a simple switch. Simply
speaking; it completes
the operation automatically started by us manually so as not to hold the push
button all the times.
5.3.2 CONTROL THE
TRIPPING
Initiate Trip Stroke: Means must be provided to trip the breaker. This may involve
energizing a solenoid coil to trip a latch or in case of air blast breakers, to
admit air to the blast valves and contacts.
Cut-Off: For the reasons noted in above, means must be provided
to automatically disconnect the trip coil.
5.3.3
TRIP FREE FEATURE
When closing a breaker, the closing device (for
example, the solenoid in a solenoid-operated breaker) is energized and the
plunger operates through the linkage to close the breaker contacts. At the end
of the closing stroke, appreciable time is required to de-energize the solenoid
coil. In the event that the breaker has been close on a faulted circuit, it
must be reopened as quickly as possible. If a breaker can trip automatically
upon receiving a trip signal before closing operation is complete, it is said
to be “trip free”.
Various arrangements are provided to obtained
trip-free action. Solenoid-operated breakers are sometimes provided with
action. Solenoid-operated breakers are sometimes provided with a collapsible
linkage. Pneumatically-operated breakers may be equipped with two latches, one
of which is unlatched during a normal trip operation and the other is only
unlatched for a trip signal while the breaker is closing. Other breakers use a
large dump valve to quickly exhaust the air under the closing piston. Many
motor-operated breakers obtain a fast trip-free action by use of a relay
energized from the trip circuit to open the closing circuit. These methods
would be known as mechanically trip free, pneumatically trip free and
electrically trip free respectively.
5.3.4 ANTI-PUMPING
FEATURE
When a breaker is closed and a trip-free operation
results, the close and trip stroke will be completed in a very short time for a
modern pneumatically-operated high voltage breaker, the complete operation will
take less than one-half of one second, thus it is quite likely that the
operator will still have the control switch in the closed position. Means must
therefore be provided to prevent the breaker from closing a second time, even
though the operator is holding the control switch in the closed position. This
is usually accomplished by the use of a sealed in relay which can only be
released which in the closed position. This is usually accomplished by the use
of a sealed in relay which can only be released by opening the closing control
switch. When this feature is incorporated in the control circuit, the breaker
is said to be “pump free” or “anti-pumping”. Following a trip-free
operation of the breaker, the operator must release the control switch before a
second attempt to close the breaker can be made.
5.3.5
ANTI-SLAM FEATURE
This feature prevents the energization of closing coil
or tripping coil of an already closed breaker or tripped breaker respectively.
1.
In closing
circuit this feature is mostly achieved through auxiliary switch b.
2.
In opening
circuit, this feature is mostly achieved through auxiliary switch a.
5.3.6
RELIABILITY
A circuit breaker is a protective device. It will be
called upon to open faulty circuits infrequently, however while it may stand
inoperative for long periods; it must be relied upon to operate correctly in
time of trouble. Reliability for such a protective device is essential. For
this reason a battery supply is always used to provide the tripping power and
in most cases for closing.
The control circuits usually have a separate trip and
close bus. This is to give extra reliability to the trip circuit. On 115 kV and
above circuit breakers there are dual trip buses thus, if a closing control
circuit fuse fails during a closing stroke, the trip circuit or circuits are
not affected.
The above requirement of extra reliability during
tripping is also seen in the size of fuses used in the trip and closed
circuits, for example, on a solenoid-operated breaker the fuses in the closing
circuit will be rated at slightly less than value of current obtained by
dividing the voltage by resistance. The fuses must be so rated to provide a
measure of protection for the short time rated closing coil. During a normal
closing operation, the closing coil will be energized for less than one second.
To have the closing fuses blow in approximately six seconds, it is necessary to
use a size which is actually less than the maximum current that the closing
coil will normally draw. Conversely, in the trip circuit the fuses will be
rated at several times the current obtained by voltage to resistance ratio. If
the trip coil is not automatically disconnected at the end of the trip stroke,
the trip coil may carry current for a long period and being are short time
rated coil, it will be damaged. The fuses in this circuit will open only due to
some fault condition. In order to gain more reliable tripping, we do not
protect the short time rated trip coil. The trip fuses are not put in the
breaker but are located in the control building.
5.3.7 GENERAL
MAINTENANCE OF BREAKER CONTROL RELAYS
Frequent reference is made in this reference material
to relays. These are control relays located in the operating mechanism housing.
They are concerned entirely with the sequence of the mechanism of the breaker.
The control circuit relays are all located on the breaker side of the four-pole
isolating switch. Such relays are a part of the breaker, being required for the
breaker’s correct functioning as much as possible, for example, a trip coil or
interrupter and as such are the responsibility of the maintenance electrician.
Other relays remote from the breaker determine under
what system conditions the breaker will be tripped. These protective relays,
together with the interposing relays where such are used, form the protective
network and are the responsibility of the Meter and Relay Department. The
dividing line between the breaker control circuit relays and protective relays
is well defined and there should be not confusion in this regard.
5.3.8
ASA DEFINATIONS
RELAY: A relay is a device that is operative by a
variation in the conditions of one electric circuit to effect the operations of
other devices in the same or another electric circuit.
CONTROL RELAY: A control relay is a relay which
functions to initiate or to permit the next desired operation in a control
circuit or scheme.
PROTECTIVE RELAY: A protective relay is a
relay, the principal function of which is to protect service from interruption
by removing defective components or to prevent or limit damage to apparatus.
5.4 OVERLOAD PROTECTION
In order to avoid damage to motors etc. due to
temperature rise because of overloading and defective bearings etc., overload
protection features are incorporated in motor control circuits. It should be
noted that over load relay or element is always incorporated in the power
circuit but its contact is installed in the control circuit. Due to this, the
life of contact increases as it breaks small current because in control circuit
current is small. Over load relays are mostly operated thermally and may be of
bimetallic strip type or solder pot type.
5.5 OVER CURRENT OR SHORT CIRCUIT PROTECTION
The function of over current
protective devices is to protect motors and its circuit elements etc. from
damage in case of phase-phase short circuits or phase-ground faults etc. The
over-current device must be capable of carrying the starting current of motors.
Mostly fuses and magnetic devices are used as over current protective devices.
Rating of fuse should not exceed 300% of full load current.
5.6
CONTACTOR
Contractor is a device which is
operated electrically and controlling the operation of other circuits
magnetically. Contactor may also be called as an ON-OFF Switch. Contactor has
two types of contacts:
1. Main Contacts: These are used in power circuits and hence must be strong
to carry the full load current of motor continuously without undue heating.
2. Auxiliary Contacts: These are small and used in control circuits only. These
may be NO or NC and are used as seal in contact (NO), interlocking contact (NC)
and for indications etc.
5.7
MAINTENANCE OF CONTACTOR
Contactor
maintenance mainly includes
1. Removal of rust or deposits etc.
from contacts with emery paper and dry cloth. Never file the contacts as it
will remove the elkonite from the contacts.
2. Checking of contacts alignment
3. Free movement of moving contacts
assembly with binding etc.
4. Checking of connections at terminal
points.
0 comments:
Post a Comment