Capicitor Application Issues
Capacitors must be built to tolerate voltages and currents in excess of their ratings according to standards. The applicable standard for power capacitors is IEEE Std 18-2002, IEEE Standard for Shunt Power Capacitors.
Heat as one of most common cause of motor failure
This slide speaks about that how motor operation fails due to heat. how heat affect motors?
Saturday, 18 July 2015
1. Why almost all large size Synchronous machines are constructed with rotating field system type?
13:59
No comments
The following are the principal advantages of the rotating field system type construction of Synchronous machines:
· The relatively small amount of power, about 2%, required for field system via slip-rings and brushes.
· For the same air gap dimensions, which is normally decided by the kVA rating, more space is available in the stator part of the machine for providing more insulation to the system of conductors, especially for machines rated for 11kV or above.
· Insulation to stationary system of conductors is not subjected to mechanical stresses due to centrifugal action.
· Stationary system of conductors can easily be braced to prevent deformation.
·
It is easy to provide cooling arrangement for a stationary system of conductors.
· Firm stationary connection between external circuit and system of conductors enable he machine to handle large amount of volt-ampere as high as 500MVA.
Friday, 17 July 2015
Generator Protection
05:49
No comments
Generator Protection
GENERATOR AND ITS PROTECTION
The
core of an electrical power system is the generator. There are power
units based on steam, gas, naphtha, water power, diesel engine drive and
wind mills. The range of size extends from a few hundred KVA (or even
less) for engine-driven and hydro sets up to turbine driven sets
exceeding 500MVA in rating.
Small and medium sized sets may be directly connected to the
distribution system. A larger unit is usually associated with an
individual transformer, transmission system. No switchgear is provided
between the generator and transformer may be tapped off the
interconnection for the supply of power to auxiliary plant. Provision of
a breaker in between Generator and Transformer makes it possible to
draw power for the auxiliaries through the UAT from the EHV bus, even
when machine is not in service. Typical arrangements are given in
figure............
Protection of 6.6 KV system in generating stations:
Major
Thermal Stations auxiliaries are fed from 6.6 KV bus which is connected
by a 220/6.6KV Station Transformers and Generation voltage/6.6 KV Unit
Auxiliary Transformers.
Station Transformers:
The vector group of these transformers is Star-Delta i.e. the 6.6 KV system is delta connected Or The vector group of these transformers is Star-Star with the 6.6KV side grounded through a high resistance.
Unit Auxilary Transformers :
The vector group of these transformers is Delta – Star (ungrounded Star on 6.6KV System).Any earth fault on the 6.6 KV system cannot be seen by any E/L relay (since the 6.6
KV system is delta connected or high resistance grounded or ungrounded
Star).However 3-O/L relays are provided on the 6.6KV side of the Station
Transformers and Unit Auxilary Transformers . An open-delta voltage of
the 6.6 KV bus PT is connected to an over voltage relay with a very low
setting. Any earth fault on the 6.6 KV system will cause the presence of open-delta voltage and make the voltage relay operate which is connected to give alarm. The faulty 6.6 KV feeder can be identified by tripping the 6.6 KV outlets one after the other.
Generator Protection – Various Functions
Generating units are the source of the power system and their security
against any adverse conditions is most important in the system. The
generator protection must ensure a fast and selective detection of any
fault in order to minimize their dangerous effects.
Protection of passive elements like transmission lines and transformers
is relatively simple which involves isolation of faulty element from the
system, whereas protection of generators involves tripping of generator
field breaker, generator breaker and turbine.
Generator Protections are broadly classified into three types.
CLASS – A :- This
covers all electrical protections for faults within the generating unit
in which generator field breaker, generator breaker and turbine should
be tripped.
CLASS – B:- This
covers all mechanical protections of the turbine in which turbine will
be tripped first and following this generator will trip on reverse power
/ low forward power protections.
CLASS – C:- This
covers electrical protection for faults in the system in which
generator will be unloaded by tripping of generator breaker only. The unit will come to house load operation and the UAT will be in service. Various protections of this class are:
i) 220 KV (HV side of Generator Transformer) busbar protection.
ii) Generator Transformer HV side breaker pole discrepancy.
iii) Generator negative phase sequence protection
iv) Generator Transformer over current / Earth fault protection
v) Reverse power protection without turbine trip.
1) Generator Differential Protection (87 G): -
It is unit type
protection, covering the stator winding for phase to phase faults due
to breakdown of insulation between stator phase windings. This relay is
not sensitive for single line to earth faults as the earth fault
current is limited due to the high neutral earthing resistance.
If CTs of
identical ratios are used on neutral and line side of generator, an
operating current setting of 20% it can be adopted. It is instantaneous
in operation and it trips the generator breaker (Class – A) to
eliminate the system in – feed to the fault along with field breaker and
turbines.
For all machines of ratings 10 MVA and above, this protection shall be provided.
2) Generator – Transformer Differential Protection (87T):-
This
is similar to Generator Differential Protection, which covers from the
generator terminals upto the HV breaker of generator transformer. . Sometimes this relay is not provided where Generator and Generator Transformer Overall Differential relay (87O) is provided. 87G & 87T functions should have the features of through fault restraint, magnetising inrush restraint.
3) Generator & Generator Transformer Overall Differential Protection (87O):
Besides
generator differential and generator transformer differential, an
overall differential relay can be provided between generator neutral
side CTs and generator transformer Hv side CTs (and HV side CTs of UAT
if provided) covering both generator and generator transformer. The principle of operation of above relay is similar to any differential relay and it is also termed as unit differential relay.
4) Backup impedance Protection (21G):-
This
operates for phase faults in the unit, in the HV yard or in the adjacent
transmission lines, with a suitable time delay. It operates as a backup when the corresponding main protection fails.
5) Voltage restrained overcurrent protection (51 / 27 G):-
This will
operate when the fault current from the generator terminals becomes low
due to excitation system characteristic with under voltage criteria.
It operates as a backup protection for system faults with suitable time delay.
6) Negative phase sequence protection (46 G):-
It safeguards
the generator rotor against over heating caused by the induced double
frequency (100 Hz) currents when negative phase sequence currents are
present in the stator. The negative phase sequence current(I2) can
appear due to unbalanced single phase loads or transmission line
unsymmetrical faults
It should be set according the Negative Phase Sequence capability of the generator
I2**2 xt = 30 for Thermal Units
= 40 for Hydro Units
Alarm stage can be set at 50% of continuous withstand capability of the machine with a time delay of 3 to 5 Sec.
7) Generator overloads protection (51G);-
It is used as an additional check of the stator winding temperature high protection. The relay can be connected
For alarm with a setting of 110% .
For trip with a setting of 125% with due time delay
8) Generator Stator Earth Fault Protection (64G):-
The high
neutral earthing resistance arrangement limits the generator earth fault
current, minimising the damage to core laminations. Although a single
phase earth fault is not critical, it requires clearance within a short
time due to:
i) It may develop into a phase to phase fault
ii) If a second earth fault occurs the current is not longer limited by the earthing resistor.
iii) Fire may result from earth fault arc.
a) 95% stator earth fault protection (64G1)
It
is an over voltage relay monitoring the voltage developed across the
secondary of the neutral grounding transformer in case of ground
faults. It covers generator, LV winding
of generator transformer and HV winding of UAT. A pickup voltage
setting of 5% is adopted with a time delay setting of about 1.0
Sec. For all machines of ratings 10 MVA and above this shall be
provided.
b) 100% stator earth fault protection (64G2);-
This is a 3rd harmonic
U/V relay. It protects 100% of stator winding.During the machine
running condition there will be certain third harmonic voltage at
neutral side of the generator.This 3rd harmonic
voltage will come down when a stator earth fault occurs causing this
relay to operate. This shall have voltage check or current check unit,
to prevent faulty operation of the relay at generator stand still or
during the machine running down period.
9) Loss of Excitation (40G):-
In
case of loss of excitation, the generator goes out of synchronism and
starts running asynchronously at a speed higher than the system,
absorbing reactive power from the system. Under these conditions, the stator end regions and part of the rotor get over heated.
This protection shall have:
i) Mho characteristic lying in 3rd and 4th quadrants of impedance diagram with adjustable reach and offset.
ii) An under voltage and / or overcurrent relay as additional check.
iii) A timer with adjustable range of 1-10 Sseconds.
Recommended Settings:-
- Diameter of Mho circle =Xd
- Off set of Mho circuit from the origin = xd1/2
- Time delay = 1 Sec.
- Under voltage relay = 110 – 115% of
generator rated current
10) Low Forward Power Relay (37G):-
In
thermal machines, when the steam flow through turbine is interrupted by
closing the ESVs or the governor valves, the remaining steam in the
turbine generates (low) power and the machine enters to motoring
conditions drawing power from the system. This protection detects low
forward power conditions of the generator and trips generator breaker
after a time delay, avoiding motoring of generator
The low forward power relay will be provided with ‘turbine trip’ interlock in thermal machines. A setting of 0.5% of rated active power of generator with a time delay of 2.0 Sec. shall be adopted.
11) Reverse Power relay (32G):-
Reverse power protection shall be used for all types of generators. When the input to the turbine is interrupted the machine enters into motoring condition drawing power from the system. Reverse power relay protects the generators from motoring condition. In thermal machines, reverse power condition appears subsequent to low forward power condition.
For reverse power relay, a setting of 0.5% of rated active power of generator with 2 stage timer as given below.
i) Stage – I: - With turbine trip interlock, a time delay of 2 Sec. shall be adopted.
ii) Stage – II:- Without ‘ turbine trip’ interlock, a time delay of about 20
Sec. can be adopted to avoid unnecessary tripping of unit during system
disturbance causing sudden rise in frequency or power swing conditions.
12) Rotor earth fault protection: -
This protection shall be provided for machines of all sizes. This
protection shall be connected for alarm and the operator may take the
machine at the earliest opportunity after the first earth fault has
occurred.
This protection will have a sensitive voltage function
operating on bridge measurement basis with auxiliary equipment. It will
have two levels, one for alarm and one for trip. The settings adopted in general are:
i) For alarm : 25 KJ Ohm, 1.0 Sec.
ii) For trip : 5 K Ohm, 0.5 Sec.
A modern generating unit is a complex system comprising the generator stator winding and associated transformer and unit transformer, the rotor with its field winding and exciters, and the turbine and its associated condenser and boiler complete with auxiliary fans and pumps. Faults of many kinds can occur within this system for which diverse protection applied will be governed by economic considerations, taking into account the value of the machine and its importance to the power system as a whole
13) Pole Slip Relay (98 G):
The pole slipping relay is designed to protect synchronous generators against the possibility of
the machine running unstable region of the ‘power angle curve’ which would result in power
oscillations and pole slip. Pole slipping of generators with respect to the system leading to an
increase in rotor angular position beyond the generator transient stability limits. Some of the
causes for pole slipping are as follows.
i) Large network disturbance
ii) Faults on the network close to the generator.
iii) Loss of generator field.
iv) Operating the generator in an excessive under excited mode.
v) Loss of evacuation.
Setting recommendations:-
a) If the source of oscillation lies between generator/transformer unit, the machine has to be
isolated from the network after the first slip.
Forward reach of relay characteristics shall cover generator/generator transformer. Tripping in this zone shall be in the first pole slip. The reach of this zone is =0.7x d’
b) If the source of oscillation lies outside the unit in the network, the generator should not be
switched off until several pole slips have recurred.
14) Generator Under Frequency Protection (81 G):
The Under Frequency Protection:
- Prevents the steam turbine and generator from exceeding the permissible operating time at reduced frequencies.
- Ensures that the generating unit is separated from the network at a preset value of frequency.
- Prevent overfluxing (v/f) of the generator (large overfluxing for short times).
The stator under frequency relay measures the frequency of the stator terminal voltage.
Setting Recommendations:-
For Alarm : 48.0 Hz, 2.0 Sec. time delay.
For Trip : 47.5 Hz, 1.0 Sec. (or)
As recommended by Generator Manufacturers.
15) Generator Over voltage Protection (59 G):
An over voltage on the terminals of the generator can damage the insulator of the generator,
bus ducting, breakers, generator transformer and auxiliary equipment. Hence over voltage
protection should be provided for machines of all sizes.
Settings recommendations:-
Stage-I : Over voltage pickup = 1.15 x Un
Time delay = 10 Sec.
State-II : Over voltage pickup = 1.3 x Un
Time delay = 0.5 Sec.
16) Standby Earth Fault Protection (51 NGT)
This relay monitors the current in the generator transformer neutral. It can detect earth faults in
the Transformer HV side or in the adjacent network.
Setting recommendations:-
As this relay pickup for faults in the system, it has to be time graded with the transmission lines
emanating from that generating station. Normally IDMT relay is provided
Operating Current Setting = 20% In
Operating Time = 1.5 to 2.0 Sec.
(or)
Greater than (max.) Zone-3 time of adjacent
Transmission Lines.
The following hazards require consideration.
a) Stator insulation faults
b) Overload
c) Overvoltage
d) Unbalanced loading
e) Rotor faults
f) Loss of excitation
g) Loss of synchronism
h) Failure of prime mover
i) Low vacuum
j) Lubrication oil failure
k) Loss of boiler firing
l) Overspeeding
m) Rotor distortion
n) Difference in expansion between rotating and stationary parts
o) Excessive vibration
Small capacity induction generators also are in service, mostly mini hydel and windmills of
capacity of 200KW to 2000KW, which depend on the system for excitation. Their protection
requirements are very simple such as overcurrent relays.
The protective relays generally used for the synchronous generators are listed at in the
following page.
Instead of independent relays for each function, microprocessor based numerical relay,
Comparision of Direct-on-line (DOL) and Star-delta Motor Starting
05:07
1 comment
Motor starting methods
Direct-on-line starting (DOL)
As the name suggests, direct-on-line starting means that the motor is started by connecting it directly to the supply at rated voltage. Direct-on-line starting, (DOL), is suitable for stable supplies and mechanically stiff and well-dimensioned shaft systems – and pumps qualify as examples of such systems.
Line diagram for Direct-on-line motor starting |
Where:
- K1 – Main contactor
- MV1 – Overload relay
Advantages of DOL
DOL starting is the simplest, cheapest and most common starting method. Furthermore it actually gives the lowest temperature rise within the motor during start up of all the starting methods.
It is the obvious choice wherever the supply authority’s current limiting restrictions allow for its use.
Power plants may have varying rules and regulations in different countries. For example:Three-phase motors with locked-rotor currents above 60 A must not use direct-on-line starting in Denmark. In such cases, it will obviously be necessary to select another starting method.
Motors that start and stop frequently often have some kind of control system, which consist of a contactor and overload protection such as a thermal relay
DOL curve – Synchronous speed / Full-load torque |
.
Drawbacks of DOL
Small motors which do not start and stop frequently need only very simple starting equipment, often in the form of a hand-operated motor protection circuit breaker.
Full voltage is switched directly onto the motor terminals. For small motors, the starting torque will be 150% to 300% of the full-load value, while the starting current will be 300% to 800% of the full-load current or even higher.
DOL curve – Synchronous speed / Full-load current |
Star-delta starting
The objective of this starting method, which is used with three-phase induction motors, is to reduce the starting current.
In starting position, current supply to the stator windings is connected in star (Y) for starting. In the running position, current supply is reconnected to the windings in delta (∆) once the motor has gained speed.
Line diagram for star-delta motor starter |
Advantages of Y-Δ
Normally, low-voltage motors over 3 kW will be dimensioned to run at either 400 V in delta (∆) connection or at 690 V in star (Y) connection. The flexibility provided by this design can also be used to start the motor with a lower voltage. Star-delta connections give a low starting current of only about one third of that found with direct-on-line starting.
Star-delta starters are particularly suited for high inertias, where the load are initiated after full load speed.
Start-delta starter curve – Synchronous speed / Full-load torque |
But they also reduce the starting torque to about 33%. The motor is started in Y-connection and accelerated and switched to the star-delta connection. This method can only be used with induction motors that are delta connected to the supply voltage.
- If the changeover from star to delta takes place at too low a speed, this can cause a current surge which rises almost as high as the corresponding DOL value. During the even small period of switch over from start to delta connectionthe motor looses speed very rapidly, which also calls for higher current pulse after connection to delta.
Star-delta starter curve – Synchronous speed / Full-load current |
Starting torque and current are considerably lower at star-delta starting than at direct-on-line starting: one third of the equivalent DOL value.
Mismatching of motor torque speed curve and load torque speed curve. In the example shown here, the motor would slowly accelerate up to approximately 50 per cent rated speed.
Mismatching of motor torque speed curve and load torque speed curve |
Comparision of DOL and Star-delta starting
The following graphs illustrate currents for a Grundfos CR pump started with a Grundfos MG 7.5 kW motor by means of DOL and star-delta starting, respectively. As you will see, the DOL starting method features a very high locked-rotor current which eventually flattens and becomes constant.
Direct-on-line starting of a Grundfos 7.5 kW motor installed on a Grundfos CR pump |
The star-delta starting method features a lower locked-rotor current, but peaks during the starting process as the changeover from star to delta is made.
When starting in star (t = 0.3 s), the current is reduced.
Star-delta starting of a 7.5 kW Grundfos motor installed on a Grundfos CR pump |
However, when switching over from star to delta (at t = 1 .7 s), the current pulse reaches the same level as the locked-rotor current seen with direct-on-line starting. The current pulse can even get higher, because the motor during the switching period is un-powered which means it reduce speed before the full voltage (delta voltage) are supplied.
Subscribe to:
Posts (Atom)